Sanpress cross T-piece with SC‑Contur
for pipe crossing while keeping required installation height
Trade mark rights exist for this document; for further information, go to viega.com/legal .
The information in this manual is directed at heating and sanitary professionals and trained personnel.
Individuals without the abovementioned training or qualification are not permitted to mount, install and, if required, maintain this product. This restriction does not extend to possible operating instructions.
The installation of Viega products must take place in accordance with the general rules of engineering and the Viega instructions for use.
Warning and advisory texts are set aside from the remainder of the text and are labelled with the relevant pictographs.
This symbol warns of possible life-threatening injury.
This symbol warns of possible serious injury.
This symbol warns of possible injury.
This symbol warns of possible damage to property.
This symbol gives additional information and hints.
This instruction for use contains important information about the choice of product or system, assembly and commissioning as well as intended use and, if required, maintenance measures. The information about the products, their properties and application technology are based on the current standards in Europe (e.g. EN) and/or in Germany (e.g. DIN/DVGW).
Some passages in the text may refer to technical codes in Europe/Germany. These should serve as recommendations in the absence of corresponding national regulations. The relevant national laws, standards, regulations, directives and other technical provisions take priority over the German/European directives specified in this manual: The information herein is not binding for other countries and regions; as said above, they should be understood as a recommendation.
Agree the use of the model for areas of application and media other than those described with Viega.
The cross T-piece is especially suitable for maintaining the floor construction height at pipe crossings.
Article number | d1 | d2 |
---|---|---|
493 325 | 15 | 15 |
493 332 | 18 | 15 |
493 356 | 22 | 15 |
493 349 | 22 | 18 |
Permissible operating temperature |
---|
Permissible operating pressure |
Thermal conductivity class of the insulating box |
110 °C |
1 MPa (10 bar) |
035 |
Lay the pipelines stress-free. The pipeline must be able to move freely at all times as a result of changes in length. Pipes running next to, above and across one another must not touch, also due to expansion. Arrange the pipe fasteners so that they do not become fixed points.
When turning the cross T-pieces, pay attention to the flow (V) and return (R) outlets.
Protect bare pipes and press connectors from external and mechanical properties.
If pipelines are laid on a load-bearing substrate, define the pipelines.
To support the insulating layer – or at least the footfall sound insulation as a minimum requirement – level the surface once again with a compensating material. Only use bonded fill for levelling above the pipelines.
The Z dimensions can be found at www.viega.de .
Requirements:
The pipe end is not bent or damaged.
The pipe is deburred.
The correct sealing element is in the press connector.
EPDM = polished black
FKM = matt black
Push the press connector onto the pipe as far as it will go.
Mark the insertion depth.
Place the press jaw onto the press machine and push the retaining bolt in until it clicks into place.
Observe the press tool instruction manual.
Open the press jaw and place it at a right-angle onto the press connector.
Check the insertion depth using the marking.
Ensure that the press jaw is placed centrally on the bead of the press connector.
Carry out the pressing process.
Open and remove the press jaw.
Connection is pressed.
Separate the product and packaging materials (e. g. paper, metal, plastic or non-ferrous metals) and dispose of in accordance with valid national legal requirements.