Easytop XL CRV slanted seat valve (combined free flow valve with backflow preventer) with flange connection
for potable water installation
Year built (from): | 1.4.2017 |
Trade mark rights exist for this document; for further information, go to viega.com/legal .
The information in this manual is directed at heating and sanitary professionals and trained personnel.
Individuals without the abovementioned training or qualification are not permitted to mount, install and, if required, maintain this product. This restriction does not extend to possible operating instructions.
The installation of Viega products must take place in accordance with the general rules of engineering and the Viega instructions for use.
Warning and advisory texts are set aside from the remainder of the text and are labelled with the relevant pictographs.
This symbol warns of possible life-threatening injury.
This symbol warns of possible serious injury.
This symbol warns of possible injury.
This symbol warns of possible damage to property.
This symbol gives additional information and hints.
This instruction for use contains important information about the choice of product or system, assembly and commissioning as well as intended use and, if required, maintenance measures. The information about the products, their properties and application technology are based on the current standards in Europe (e. g. EN) and/or in Germany (e. g. DIN/DVGW).
Some passages in the text may refer to technical codes in Europe/Germany. These should serve as recommendations in the absence of corresponding national regulations. The relevant national laws, standards, regulations, directives and other technical provisions take priority over the German/European directives specified in this manual: The information herein is not binding for other countries and regions; as said above, they should be understood as a recommendation.
The following standards and regulations apply to Germany / Europe and are provided as a support feature.
Scope / Notice | Regulations applicable in Germany |
---|---|
Planning, execution, operation and maintenance of potable water installations | DIN EN 806, part 1 |
Planning, execution, operation and maintenance of potable water installations | DIN EN 806, part 2 |
Planning, execution, operation and maintenance of potable water installations | DIN EN 806, part 3 |
Planning, execution, operation and maintenance of potable water installations | DIN EN 806, part 4 |
Planning, execution, operation and maintenance of potable water installations | DIN EN 806, part 5 |
Planning, execution, operation and maintenance of potable water installations | DIN EN 1717 |
Planning, execution, operation and maintenance of potable water installations | DIN 1988 |
Planning, execution, operation and maintenance of potable water installations | VDI/DVGW 6023 |
Planning, execution, operation and maintenance of potable water installations | Trinkwasserverordnung (TrinkwV) |
Scope / Notice | Regulations applicable in Germany |
---|---|
Suitability for drinking water | Trinkwasserverordnung (TrinkwV) |
Scope / Notice | Regulations applicable in Germany |
---|---|
Suitability for drinking water installations | Trinkwasserverordnung (TrinkwV) |
Suitability for drinking water installations | DIN 50930‑6 |
Requirements in plastic components in drinking water installations | DVGW-Arbeitsblatt W270 |
Scope / Notice | Regulations applicable in Germany |
---|---|
Compliance with the inspection requirements (fittings group I) | DIN EN 1213 |
Scope / Notice | Regulations applicable in Germany |
---|---|
EA marking for classification | DIN EN 1717 |
Scope / Notice | Regulations applicable in Germany |
---|---|
External corrosion protection | DIN EN 806‑2 |
External corrosion protection | DIN 1988‑200 |
External corrosion protection | DKI-Informationsdruck i. 160 |
Scope / Notice | Regulations applicable in Germany |
---|---|
Leakage test for potable water installations | DIN EN 806, part 4 |
Leakage test for potable water installations | ZVSHK-Merkblatt |
Scope / Notice | Regulations applicable in Germany |
---|---|
Operation and maintenance of potable water installations | DIN EN 806‑5 |
Coordinate the use of the model for areas of use and media other than those described with the Viega Service Center.
Use is possible in the following areas among others:
Drinking water installations
Industrial units
The general rules of engineering and the applicable regulations must be observed for planning, execution, operation and maintenance potable water installations, see Regulations from section: Fields of application .
The model is also suitable for the following media, amongst others:
Drinking water without limitations acc. to the applicable directives, see Regulations from section: Media
maximum chloride concentration 250 mg/l pursuant to applicable regulations, see Regulations from section: Media
According to the applicable regulations, Easytop system fittings can be used for all types of potable water and are DVGW certified, see Regulations from section: Product description . Their plastic components comply with the KTW recommendation and the requirements pursuant to the applicable regulations.
The Easytop system fittings comply with the test requirements specified in the applicable regulations, see Regulations from section: Overview . Sound protection Lap≤ 20 dB(A)
The model is equipped as follows:
valve casing made of gunmetal/silicon bronze
valve top made of gunmetal/silicon bronze (dead space free)
dual-sided flange connection pursuant to applicable regulations, see Regulations from section: Overview
valve seat and valve plate unit made of stainless steel
non-rising spindle
position indication open/closed
handwheel with exchangeable coloured plastic cap as media labelling
combined backflow preventer (CBP)
drainage / testing plugs G ¼ upstream and downstream from the backflow preventer for DN 50
drainage / testing plugs G ⅜ upstream and downstream from the backflow preventer for DN 65, 80, 100
valve and spindle seal made of EPDM (maintenance-free)
The model is fitted with a backflow preventer.
Backflow preventers only allow flowthrough in one direction (in the direction of flow). If the direction of flow changes, e.g. due to back suction, the backflow preventers close automatically.
The model is available in the following dimensions: DN 50 / 65 / 80 / 100
The model is marked as follows:
flow direction indicator
dimension
DVGW writing
position indicator below the handwheel, with CRV writing
EA marking for classification in accordance with the applicable regulations, see Regulations from section: Marking on components
The model is compatible with the Profipress / Profipress XL, Sanpress / Sanpress XL and Sanpress Inox / Sanpress Inox XL system.
Backflow preventers protect fittings and installation systems against unintended backflow, back pressure or back suction of the contaminated wastewater or dirty water in the piping system. This can occur after pressure fluctuations in the distributor circuit, which can cause a change in the direction of flow.
The backflow preventer prevents the pushing back, backflow or back suction of liquids, which may be a health hazard, into the public drinking water network, with the help of a spring-loaded valve cone. The dimension is dependent on the peak pressure and it complies with the nominal width of the pipeline. The backflow preventer must be fitted with testing equipment.
In many countries, standards and technical guidelines stipulate the use of backflow preventers or other suitable safety equipment that protect drinking water against contamination.
Observe the following operating conditions for the installation of the model:
Operating temperature [Tmax] |
---|
Operating pressure [Pmax] |
90 °C |
1.6 MPa (16 bar) |
The performance diagram shows the pressure losses (in hPa) in relation to the volume flow and the nominal width.
Overground pipelines and fittings in rooms do not normally require external corrosion protection.
There are exceptions in the following cases:
Contact with aggressive building materials such as nitrite or materials containing ammonium
in aggressive surroundings
If external corrosion protection is required, observe the pertinent guidelines, see Regulations from section: Corrosion .
Easytop fittings made of gunmetal/silicon bronze are suitable for all types of potable water.
The chloride concentration in the medium must not exceed a maximum value of 250 mg/l.
This chloride is not a disinfectant, but in fact pertains to the content in sea and table salt (sodium chloride).
The following optional accessories are available:
Drainage valves
Mounting sets
Seals
Do not remove the model from the packaging until immediately before use.
System components may, in some cases, become damaged through transportation and storage.
Check all parts.
Replace damaged components.
Do not repair damaged components.
Contaminated components may not be installed.
Observe the following when mounting:
flow direction indicator
use suitable tools
Choose the place of installation so that the fitting is easily accessible and simple to operate.
For information, refer to the instructions for use of the Profipress / Profipress XL, Sanpress / Sanpress XL and Sanpress Inox / Sanpress Inox XL systems.
For information, refer to the instructions for use of the Profipress / Profipress XL, Sanpress / Sanpress XL and Sanpress Inox / Sanpress Inox XL systems.
The installer must perform a leakage test before commissioning.
Carry out this test on a system that is finished but not yet covered.
Comply with the general rules of engineering and the applicable directives, see Regulations from section: Leakage test .
Document the result.
Inform your customer or the operator of the drinking water installation that the system has to be maintained on a regular basis.
Observe the applicable regulations for the operation and maintenance of drinking water installations, see Regulations from section: Maintenance .
Viega recommends actuating the fitting regularly and checking its function.
If the valve top needs to be replaced, model 2238.8XL can be used.
Separate the product and packaging materials (e. g. paper, metal, plastic or non-ferrous metals) and dispose of in accordance with valid national legal requirements.